F9 Pocket / Bag Filters — AHU Secondary Filtration, South Africa

The Airtech pocket filter range — for commercial and industrial AHU applications. Synthetic media, multi-pocket construction, galvanised steel and aluminium support frames in all standard AHU sizes. For commercial offices, healthcare general areas, pharmaceutical production and critical commercial buildings. Stock held in Pretoria; call with your AHU frame size and pocket count and we confirm availability the same day.

Get a Quote Download Datasheet

Airtech Pocket Filter Grade

F9 — Final filtration for pharmaceutical production areas, hospital theatres and antechambers, ISO 8 cleanroom supply air, and high-specification commercial buildings requiring low particulate counts. EN779 F9 ≥95% average efficiency at 0.4µm.

Not sure which grade you need? Call Nick Els on +27 74 159 1634 — describe the application, building type, and any compliance standard you are working to, and we will confirm the correct grade.

Airtech F9 pocket bag filter for HVAC secondary filtration South Africa

Technical Data

Filter Class F9 (EN779:2012)
Standard Size (330mm) 595 × 595 × 330 mm (6-pocket)
Narrow Size (330mm) 295 × 595 × 330 mm (4-pocket)
Deep Format (600mm) 595 × 595 × 600 mm (6-pocket)
Media Type Synthetic moisture-resistant
Frame Galvanised steel + aluminium supports
Initial Resistance (595×595×330) 225 Pa ±10% at 3 400 m³/h
Initial Resistance (295×595×330) 185 Pa ±10% at 1 700 m³/h
Initial Resistance (600mm) 105 Pa ±10% at 3 400 m³/h
Final Resistance 400–450 Pa (replace at this reading)
Washable No
Avg. Efficiency F9 ≥ 95% at 0.4 µm (captures PM2.5)
Weight (595×595×330) 1.7 kg
Weight (295×595×330) 1.15 kg

Resistance vs Airflow — 595×595×330mm (6-pocket)

Airflow (m³/h) 15002000250030003400400045005000
Resistance (Pa) 95125160195222266305345

Resistance vs Airflow — 595×595×600mm Deep (6-pocket)

Airflow (m³/h) 15002000250030003400400045005000
Resistance (Pa) 45607592106130150170

Applications

F9 pocket filters are the secondary filtration stage in commercial HVAC systems — the filter that determines indoor air quality. At ≥95% average efficiency at 0.4µm, F9 captures PM2.5 fine particulate, diesel combustion aerosols, and the fine dust that G4 pre-filters let through. Specified wherever occupant health, regulatory compliance, or equipment protection demands more than coarse filtration alone.

  • Commercial offices and retail — IAQ compliance and occupant comfort in high-occupancy buildings. F9 is the secondary filter standard for most commercial HVAC specifications in South Africa.
  • Hospitals and healthcare facilities — Secondary filtration upstream of H14 HEPA terminal filters in operating theatre and critical care AHU systems.
  • Pharmaceutical manufacturing — Pre-HEPA filtration in GMP Grade B and C cleanroom air handling systems to extend HEPA service life.
  • Data centres — ASHRAE TC 9.9 recommends F9 equivalent filtration for data centre air handling. F9 pocket filters with low pressure drop protect sensitive electronics from fine particulate contamination.
  • Education and hospitality — High-traffic buildings where IAQ and energy efficiency are both priorities — F9 provides the filtration performance without the pressure-drop penalty of HEPA.

Ready to order?

Local stock. Same/next-day despatch. Call Nick: +27 74 159 1634