Facilities specifying HEPA filters in South Africa face two questions before anything else: which grade the application needs, and whether the units arrive with the documents an audit will ask for. HEPA is defined by EN1822, the European standard covering high-efficiency filters, with H13 and H14 the two grades used across local cleanrooms, hospitals, and pharmaceutical plants. Prebur holds Airtech H13 and H14 HEPA in stock in Pretoria, and every unit ships with an individual serial-numbered EN1822 test certificate for the validation file.

This page covers the grade difference, where each is used, the certificate that separates HEPA from lower grades, the sizes we hold locally, and how installed filters are verified on site.

HEPA Filters in South Africa: What You Need to Know

South African facilities specify HEPA against EN1822:2019, which defines high-efficiency filter classes from E10 through U17. HEPA covers H13 and H14. Both are rated at the Most Penetrating Particle Size (MPPS), the particle diameter a filter finds hardest to catch, so passing at MPPS means the filter performs better against every other size.

For a facilities or QA reader, three things matter in practice. The grade you specify (H13 or H14) follows the application and its cleanliness class. Both grades ship with a per-unit test certificate, which is the document your validation file needs. And lead time decides whether an air handling unit sits idle: importing to order can mean weeks of waiting, while a stocked filter is already on the shelf in Pretoria.

Prebur is a direct importer and supplier of the range, not its manufacturer. The Airtech range is manufactured to EN1822 standards in an ISO 9001 facility, and we hold H13 and H14 HEPA in our Silverton, Pretoria warehouse. Owner-run since 1989, we confirm availability the same business day when you call.

Key Takeaways

  • HEPA in South Africa is defined by EN1822: H13 (>=99.95% at MPPS) and H14 (>=99.995% at MPPS).
  • H14 is commonly specified for GMP Grade A cleanrooms and operating theatres; H13 suits general hospital ventilation.
  • Every HEPA unit, H13 and H14, ships with an individual serial-numbered EN1822 test certificate.
  • Prebur holds two sizes of both H13 and H14 in stock in Pretoria, with nationwide courier delivery quoted at checkout.

H13 vs H14: Which Grade Do You Need?

The difference is a factor of ten at the filter’s weakest point. H13 removes at least 99.95% of particles at MPPS; H14 removes at least 99.995%, so roughly ten times fewer particles get through an H14. Both are genuine HEPA under EN1822, and that tenfold gap is what decides audit outcomes in sterile environments. The full derivation lives in our HEPA filter grades guide, which owns the MPPS maths.

GradeEfficiency at MPPSTypical usePer-unit certificate
H13>=99.95%General hospital ventilation, supporting cleanroomsYes: serial-numbered EN1822 certificate
H14>=99.995%GMP Grade A cleanrooms, operating theatresYes: serial-numbered EN1822 certificate

The practical rule we give callers: if the space is a Grade A sterile zone or an operating theatre, specify H14. For a supporting cleanroom or general critical ventilation, H13 usually satisfies the requirement. When you are unsure, the specifying engineer’s grade call governs, and we supply against it either way. For the reasoning behind each threshold, the grades guide sets out the numbers in full.

Where Are HEPA Filters Used?

HEPA is the final filtration stage in any space where airborne particle counts are regulated, and ordinary comfort HVAC does not need it. Comfort ventilation tops out at an F7 to F9 fine filter. HEPA is normally specified once a room is classified under ISO 14644, the cleanroom standard, or falls under GMP or infection-control rules.

The applications we supply into most often are consistent across the sector:

  • Pharmaceutical and GMP production: Grade A and B zones commonly specify H14 for sterile manufacturing. See our pharmaceutical filtration overview.
  • Hospital critical areas: operating theatres and protective isolation rooms, where infection control drives the grade. Our healthcare filtration page covers the theatre and ward split.
  • Classified cleanrooms: any space graded under ISO 14644 relies on terminal HEPA or ULPA to hold its particle count.
  • Critical AHU final stage: the last filter before supply air enters a controlled space.

HEPA is a defined stage, specified against a cleanliness class and protected by upstream G4 and F9 filters that stop it clogging early. Where a room carries a class number, the HEPA is doing defined work, and the paperwork has to prove it. For how those classes are verified on site, our ISO 14644 cleanroom testing guide walks through the method.

The Test Certificate That Comes With Every HEPA Unit

Every Airtech HEPA unit we supply, H13 and H14 alike, ships with an individual serial-numbered EN1822 test certificate. The specific unit is tested at the factory, not classified from a batch sample, and the certificate records the serial number and the overall efficiency at MPPS against the grade minimum: >=99.95% for H13, >=99.995% for H14. It goes straight into your Installation Qualification package or HVAC service log.

This is a requirement of the standard rather than a service we add on top. EN1822 requires each HEPA filter to be individually tested and marked, which is precisely what separates HEPA from the coarse and fine grades below it. G4, F9, and other non-HEPA filters are batch-classified, so they carry a grade-level CNAS laboratory test report instead of a per-unit certificate. If you are offered an individual certificate on a G4 or F9, ask what the document actually is.

For a GMP or hospital audit, that certificate is the evidence expected against each installed HEPA filter, which is why we lead with it. The filter and its paperwork arrive together, at no extra cost, ready for the validation file. The HEPA product page lists what the certificate contains.

Standard HEPA Sizes and Local Stock

We hold two sizes in Silverton, Pretoria, in both H13 and H14: the full-size 610x610x292mm (rated 3400 m3/h) and the half-size 305x610x292mm (rated 1700 m3/h). Every unit ships with the individual serial-numbered EN1822 certificate.

Size (mm)Rated airflowInitial resistanceGradeStock
610 x 610 x 2923400 m3/h290 PaH14In stock, Pretoria
305 x 610 x 2921700 m3/h300 PaH14In stock, Pretoria
610 x 610 x 2923400 m3/h260 PaH13In stock, Pretoria
305 x 610 x 2921700 m3/h280 PaH13In stock, Pretoria

The half-size format fits AHU configurations where a full-size unit would need housing modification, so confirm your housing dimensions before ordering. The units start at roughly 260 to 300 Pa and are typically replaced once resistance climbs to about 500 to 600 Pa, so track differential pressure as the trigger. Standard sizes are in stock at our Silverton warehouse, and online orders are delivered nationwide at the courier rate quoted at checkout, or you can collect. Non-standard dimensions are manufactured to order on a 7 to 10 day lead time, with availability confirmed the same business day when you call Nick on +27 74 159 1634.

Stock in Pretoria changes the downtime calculation on an AHU. A filter held on the shelf in Pretoria is available now, where a filter imported to order can leave the unit offline for weeks. You can buy H14 HEPA or H13 HEPA online, or request a quote for a custom size.

How Are Installed HEPA Filters Tested?

A HEPA filter only performs if the housing seals and the media is leak-free, so the factory certificate is one half of the picture and the installed test is the other. Once fitted, a HEPA filter is verified on site by an aerosol scan that checks for pinholes, media defects, and gasket bypass. This is a different check from the EN1822 factory efficiency test: the factory certificate qualifies the media, and the on-site scan qualifies the installation and its seal. Our ISO 14644 cleanroom testing guide covers the scan procedure and pass criteria in full, and our cleanroom testing service in South Africa sets out how to book an on-site test.

Prebur offers this as a service. Our on-site air testing verifies installed HEPA integrity, air quality, and airflow, with Grant Lundie as our technical partner. Reports are issued in accordance with the relevant ISO standard methodology. When a test finds a filter that has failed its seal or scan, the replacement is already in stock in Pretoria, so one supplier covers the verification and the filter.

For a South African project, specify the grade explicitly, “EN1822:2019 H14” or H13 where appropriate, because “HEPA” alone carries no defined efficiency threshold. For H13 and H14 filters, require the individual serial-numbered test certificate in the same line. That wording is unambiguous to contractors and gives an auditor the exact evidence to check against each installed filter.

Prebur supplies the whole airflow chain from one Pretoria warehouse: G4 and F9 pre-filters that protect the HEPA, the H13 and H14 HEPA itself, and the air testing that verifies it in place. We are a direct importer, owner-run since 1989. When you call, you speak to an owner, not a call centre, and availability is confirmed the same business day.

To source HEPA with certificates included, view the H14 or H13 product page, or call Nick Els on +27 74 159 1634. For a wider view of local filter supply, see our air filter suppliers in South Africa guide.

Frequently Asked Questions

What is a HEPA filter?

A HEPA filter is a high-efficiency air filter classified under EN1822, the European standard for HEPA and ULPA filtration. The two grades used in South African facilities are H13 (at least 99.95% efficiency at the Most Penetrating Particle Size) and H14 (at least 99.995%). They are the final filtration stage in cleanrooms, operating theatres, and pharmaceutical production.

What is the difference between H13 and H14 HEPA filters?

Both are HEPA grades under EN1822. H13 removes at least 99.95% of particles at the Most Penetrating Particle Size; H14 removes at least 99.995%, roughly ten times fewer particles getting through. H13 suits general hospital ventilation and supporting cleanrooms. H14 is commonly specified for GMP Grade A cleanrooms and operating theatres.

Do your HEPA filters come with a test certificate?

Yes. Every Airtech HEPA unit we supply, H13 and H14 alike, ships with an individual serial-numbered EN1822 test certificate for your validation file, at no extra cost. EN1822 requires each HEPA filter to be tested individually at the factory rather than classified from a batch sample, so the certificate belongs to your specific unit. Certificates are a HEPA feature: they are not supplied with G4, F9, or other non-HEPA grades, which carry grade-level CNAS laboratory test reports instead.

What HEPA filter sizes do you stock in South Africa?

We hold two sizes in both grades in Silverton, Pretoria. H14: 610x610x292mm (3400 m3/h, 290 Pa initial resistance) and 305x610x292mm (1700 m3/h, 300 Pa). H13: the same two sizes, at 260 Pa and 280 Pa. Non-standard dimensions are manufactured to order on a 7 to 10 day lead time.

Do you deliver HEPA filters nationwide?

Yes. We deliver nationwide by courier, with the delivery price quoted live for your address at checkout. You can also collect from our Silverton, Pretoria warehouse at no charge. For custom dimensions, availability is confirmed the same business day and the filter is manufactured on a 7 to 10 day lead time.

Can you test HEPA filters after installation?

Yes. Prebur offers an on-site air testing service that verifies installed HEPA filters using an aerosol scan under ISO 14644-3 methodology. Grant Lundie is our technical partner. Reports are issued in accordance with the relevant ISO standard methodology. If a filter fails, the replacement is on our shelf in Pretoria.

Written by Nick Els

Nick Els owns and runs Prebur from Silverton, Pretoria. Established in 1989, Prebur supplies air filters to facilities across South Africa. Call +27 74 159 1634.

Need help choosing the right filter?

Speak to Nick Els for expert advice on filter selection, cross-referencing, and pricing for your facility.

← Back to all articles